How should one design an 8000VA
transformer for medical premises in accordance with IEC 61558 ?
Technical specification relevant only to design
Electrical data and diagram
| Input voltages |
230Vac, sinusoidal |
| Frequency |
50Hz |
| Nominal output voltage |
230Vac |
| Nominal output current |
34.8A (8000VA) |
| Short-circuit voltage |
3% (cold, +-20%) |
| Inrush current factor |
max 8 x I^nominal |
| No-load current |
max 3% |
Ambient and operating conditions:
| Ambient temperature |
40°C |
| Mode of operation |
Continuous operation |
| Test conditions |
Non iherently short-circuit proof |
Specification

Criteria for design
IEC 61558
A non inherently short-circuit proof transformer as per IEC 61558 is equipped with a
safety. Very often, we arrive at a combined protection solution, which consists of a
primary-side fuse and a thermal cut-out. For this reason, short-circuit and overload are
not design criteria. The design criteria for purposes of IEC 61558 are temperature q nominal, the maximum permitted short-circuit voltage of 3%
and the inrush current, whose maximum level is eight times the peak value of the primary
nominal current. Since IEC 61558 permits utilization of two condensers for compensation of
the reactive no-load current, we should limit the active no-load current and iron losses
to approximately 2%, which is not usually a problem.
| Insulation class |
A |
E |
B |
F |
H |
| Max winding temperature in test q max
(° C) |
200 |
215 |
225 |
240 |
260 |
| Max winding temperature in nominal operation q nominal (° C) |
100 |
115 |
120 |
140 |
165 |
| Short-circuit voltage (%) |
<3 |
<3 |
<3 |
<3 |
<3 |
| Inrush current factor |
<8 |
<8 |
<8 |
<8 |
<8 |
| No-load current (%) |
<3 |
<3 |
<3 |
<3 |
<3 |
Insulation class
- Max winding temperature in nominal operating mode = 120°C
- ax winding temperature in test mode = 225°C
Insulation class B is prescribed.
Design criteria
Computer program employs two design criteria:
- Regulation <3%
- Temperature rise <80°K for 40°C ambient temperature and insulation class B.
Note that short-circuit voltage for a single-chamber bobbin unit is very closed to the
regulation.
Since we do not know which of these criteria will be the more relevant to our design,
we shall enter Criterion = 0 and leave it to the computer program to decide.
Bobbin unit and core.
Control transformers have to be produced with a low internal resistance and with low
scatter impedance. For this reason, transformers for medical purposes are constructed
exclusively with single-chamber bobbin units. For practical purposes, there is only one
choice of UI core form to select for the 3kVA to 10kVA output range.
Inrush current
The peak value of the inrush current, cold, in the first period after switch-on at the
zero-axis crossing point, should not exceed a factor of 8 x the peak value for
nominal input current. This can best be achieved if:
- The nominal induction is 1.1T-1.2T.
- The transformer is constructed with a defined creep distance of approx 0.05-0.10 mm,
so as to reduce residual magnetism.
- The primary winding is routed to the outside.
Induction and iron quality
Inrush-current transformers with a inrush factor of <8 are operated with a low
induction (1.0T-1.2T). For this reason, we use virtually nothing but cold-rolled
iron quality of 5.3W/kg at 1.5T, 50Hz.
Short-circuit voltage
The maximum permitted short-circuit voltage is 3%. In accordance with IEC
61558, a transformers short-circuit voltage is measured in the cold state at 20°C.
The permitted tolerance is +-20%.
The computer program calculates short-circuit voltage. However, this cannot be used as a
design criterion. We shall use regulation, since a single-chamber
transformers regulation is practically identical to its short-circuit voltage.
In the design process, regulation of 3.3% to 3.6% is used, on account of the
permitted short-circuit tolerance of +/-20%.
Procedure for design
- If you are not yet acquainted with Rale design software, please read the text
"How should I design a small transformer?". Keep a copy of this text within
convenient reach whenever performing design work.
- Fill in the design input mask as follows. If you need any help, press function key F1.
There is extensive description for each input field.

- The Selection input field is set at 0. This means that the program should
search on-line for a suitable core for this application, from your selected core family.
- Save your input data file. In this specimen design calculation, we saved the input data
in input data file CAL0008E.TK1. This input data file was supplied together with
this document. Copy it into the directory in which your Rale demo program is installed.
- Connect up to the Rale design server.
- Load up your input data file.
- Now select the UI core family and the core for automatic search by the computer program.

- Click on OK.
- Start your design work. In the system for automatic selection of the UI core from your
prescribed core family, the program will offer you an adequately sized core for your
application. Click on OK in order to accept the core.

On completion of the design work, the following design data will be available and can
bprinted on three pages:










- This is followed by checking of the design data.
- We now check the winding data and the filling factor (91.3%<100%).
- The maximum temperature of the windings is 40°C+79.0°K = 119°C < 120°C.
- Short-circuit voltage = 3.82% > 3.6% (see the corrections in the test mode).
- The inrush current factor is somewhat less than 8: 302.3A^/38.49A/1.41=5.7<8.
We could use a higher induction.
In the test program, we could manually select a lower wire thickness in the primary
winding and increase the primary winding resistance so as to reduce the inrush current. At
the same time, however, we should increase the wire thickness of the secondary winding so
that the temperature of the windings will not exceed the prescribed limits.
- Iron losses should not exceed approximately 2% of the nominal output (100*94.25W/8994VA=1.08%
< 2%).
The reactive component of the no-load current is 100*352.1VA/230V/38.59A= 3.95%.
For complete compensation, we should connect two condensers to the primary winding
terminals, and the two condensers together should compensate the transformers
no-load reactance of 176.2 Ohm: The capacitance value is Ctotal =
1/176.2/314=18µF. At approximately 6-7µF, we would be safely below 3%.
- This is followed by checking of the output voltage for a nominal input voltage of 230V:
Uin = 1. Note that the wire size of the secondary winding was changed manually in order to
get a better number of layers and to reduce the short-circuit voltage from 3.8% to 3.6%

- If the design data is not satisfactory, then there are two ways by which we can
implement the desired correction:
- You can return to the input mask (function key F2), correct the input data and redesign
the transformer.
- Or you can access the test program (function key F5), modify the designed transformer
manually and redesign the transformer by that means.
- On completion of the design work, you can print out the design data on-line, or save it
on your local PC and print it out off-line. The output data file from this design example,
CAL0008E.TK2, is supplied together with this document.
Copy it into the directory in which your Rale demo program is installed.
Tips & Tricks
The optimum solution
The optimum solution features the maximum permitted temperature and the maximum
permitted short-circuit voltage at the same time. This also means that you can use the
maximum induction in relation to the inrush current factor.