|
<Back>
How should one design
a 70kHz, 60W-120VA flyback transformer with voltage controller, for input voltage range
125V to 700V ,
as per IEC 61558 ?
Technical specification relevant only to design
Electrical data and diagram:
| Input voltages range |
125Vdc - 700Vdc (bridge rectifier with RC-load, for input
voltage 110Vac, 60Hz to 500Vac, 50Hz) |
| Frequency |
70kHz |
| Nominal output voltage |
2 x 12Vdc, automatic controlled on the primary side |
| Nominal output current |
2 x 5Adc, -50% |
| Ripple of the input current |
Max. 100% at the maximal input voltage and the nominal load |
Ambient and operating conditions:
| Ambient temperature |
40°C |
| Test conditions |
Non inherently short-circuit proof |
| Mode of operation |
Continuous |
Specification
Insulation class E
The following flyback transformer diagram illustrates only parameters relating to
design. The windings for protection and for measurement cannot be calculated by program.


With a flyback transformer, the distinction is drawn between two modes of operation:
- Mode with continuous secondary current ( Fig. 1, t3=0).
- Mode with intermittent DC secondary current (Fig. 2, t3>0).
Continuous mode (Fig.1)
In this mode, secondary current ripple is less than 100%:
Ripple = 100* (Ismax-Ismin)/(Ismax+Ismin) =(Bmax-Bmin)/(Bmax+Bmin)
< 100
In the flyback transformers continuous mode, the output voltage is
"impressed" for practical purposes, and is not greatly dependent upon load. This
mode is easy to regulate and is preferred by electronics engineers. Secondly, the flyback
transformer is larger with less ripple in the primary current. For that reason, the choice
of ripple (10% to 100%) of the secondary current has to be harmonized between the
transformer manufacturer and the electronics engineer.
Intermittent mode (Fig.2)
This mode is essentially utilized for generation of the current pulses or a high output
voltage.The following conditions are selected upon sizing:
Criteria for design
IEC 61558
A high-frequency transformer with non- inherently short-circuit proof as per IEC 61558 is
equipped with a safety. Very often we arrive at a combined protection solution consisting
of a thermal cutout in the transformer and cutout electronics in the cycled mains power
unit to protect against overload and short-circuit. For this reason, short-circuit and
overloads are not design criteria. The criterion for design with regard to IEC 61558 is
only temperature q nominal.
| Insulation class |
A |
E |
B |
F |
H |
| Max winding temperature in test q max
(° C) |
200 |
215 |
225 |
240 |
260 |
| Max winding temperature in nominal operating mode q nominal (° C) |
100 |
115 |
120 |
140 |
165 |
Insulation class
Max winding temperature in nominal operating mode = 115°C
Max winding temperature in test mode = 215°C
Insulation class E is prescribed.
Criterion for design
Normally, high-frequency transformers have very low regulation and are designed according
to the prescribed temperature rise.
Since these transformers are manufactured almost exclusively using ferrite, the optimum
operating temperature is around 100°C.
Bobbin unit
In order to protect the transistors, high-frequency transformers should be manufactured
for low leaking reactance , with single-chamber bobbin units. For this reason, we very
often arrive at bifilar or interleaved windings.
Ferrite quality
Since the optimum operating temperature of ferrite for high-frequency transformers over
100VA is around 100°C and their ambient temperature is between 40°C and 70°C, our
design assumption must be for a temperature rise of between 30°K and 60°K. If the core
losses in relation to temperature rise are not economically acceptable, then the computer
program will optimize or reduce the AC-component (the ripple of the input current) of the
induction automatically. But this does indicate that the selected ferrite quality is not
optimized.
Induction and ferrite quality
High-frequency transformers are equipped almost exclusively with ferrite. The program
calculates both the active and the reactive core losses by hypothesizing the ferrite type,
the frequency, the form of input voltage, induction and core temperature. The induction
should be selected such that the transformer does not saturate at maximum input voltage
and maximum core temperature.
Copper additional losses
With a high-frequency transformer, the distinctions are drawn between the following
additional losses in a winding, over and above the dc-current losses:
- Eddy current losses
- Displacement losses
- Proximity effect losses
- Losses due to circulating currents through the parallel-connected wires.
Additional losses are smaller in the case of a winding that takes up only 30-60% of the
available winding space. For that reason, one should always set the input for the filling
factor between 0.3 and 0.6 for purposes of automatic core selection.
The input for Rac/Rdc will limit the extent of additional losses (eddy current
losses and displacement losses). The computer program selects a high enough number of
parallel-connected wires for the eddy current losses and displacement losses to fall short
of the prescribed value for Rac/Rdc. For that reason, the input for Rac/Rdc is
also used for monitoring of parallel-connected wires. The value is normally set between
1.5 and 5.
Proximity effects can be reduced by means of the Spread input. Another option for
reducing proximity effects is to select wires with thicker insulation.
Losses of circulating currents through the parallel-connected wires are not calculated. It
is assumed that these additional losses have been eliminated by suitable design
precautions. In particular, it should be ensured, for a given litz, that the twisting for
the winding is done such that a given wire has the same position at the input and at the
output of the winding.

Nominal input voltage and relative switch-on period
The relative primary voltage switch-on period is defined as follows:

In the design of a flyback transformer, the duration of the relative switch-on period (q
= t1/(t1+t2) ) is taken into account indirectly via the input mode of the form
factor:
Form factor = 1/(2*q)
A flyback transformer with an automatic controller of output voltage is normally
designed with the following parameters:
- "Nominal" input voltage Upnom= (Upmin*Upmax)1/2 = (125*700) 1/2= 296V. At this input voltage the relative switch-on period qnom
will be 0.5.
- This flyback transformer has to be designed at the input voltage Upmin = 125V. At this
input voltage the relative switch-on period has to be prescribed via the form factor:
qmax = Unom/(Umin + Unom) = 3296/(125+296) = 0.7.
- The form factor = 1/(2* qmax) = 1/(2*0.7) = 0.711
- Th relative switch-on period at the input voltage Upmax = 700V will be:
qmin = Upnom/(Upmax+Upnom) = 296/(700+296) = 0.3
- In order to have the ripple smaller than 100% at the maximal input voltage, you have to
prescribe the ripple at the minimal input voltage as follows:
Ripplemin = Ripplemax *(Upmin*qmax/Upmax/qmin)^2
= 100*(0.7*125/750/0.3)^2 < 17%

Procedure for design
- If you are not yet acquainted with Rale design software, please read the text
"How should I design a small transformer?". Keep a copy of this text within
convenient reach whenever performing design work.
- Fill in the design input mask as follows. If you need any help, press function keys F1.
There is extensive description for each input field.

- The Selection input field is set at 0. This means that the program should
search on-line for a suitable core for this application, from your selected core family.
- Save your input data file. In this specimen design calculation, we saved the input data
in input data file CAL0010E.TK1. This input data file was supplied together with
this document. Copy it into the directory in which your Rale demo program is installed.
- Connect up to the Rale design server.
- Load up your input data file.
Now select the core family and the core for automatic search by the
computer program.

- Click on OK.
- Start your design work. In the system for automatic selection of the core from your
prescribed core family, the program will offer you an adequately sized core for your
application. Click on OK in order to accept the core.
- On completion of your design work, the following design data is available. We must not
omit to mention at this point that the calculated data for short-circuit and for idle
are not applicable to the flyback mode for this transformer (and cannot be used for that
context). However, there are two modes which relate exclusively to the flyback
transformer: primary winding inductance and the gap for calibration of the primary winding
inductance.
- On completion of the design work, the following design data will be available,
which can be printed on 3 pages.:










- Checking of the design data follows this.
- We now check the winding data and the filling factor (36.7%<100%).
- The maximum temperature of the windings is 40°C+57.9°K = 97.9°C < 115°C.
- The number of parallel-connected wires with 0.16 mm diameter is 9 and 123. Commercial
considerations prompt us to select a litz of 10 wires of 0.16 mm diameter for the primary
and a litz of 125 wires of 0.16mm for both secondary windings. This operation must be
performed manually in the test mode.
- This is followed by checking of the output voltage for the maximal input voltage of 700V
and the relative switch-on period of 0.3: Uin = 700/125 = 5.6 and form factor = 1/(2*0.3)
= 1.68.
Note that the program controls your input in order to avoid the operation in the
saturation of the core. If you get any problem with your input, follow these procedures.
- Increase the form factor to 1.68 (q = 0.3)
- Press F6 to recalculate
- Increase the input voltage to 700V : Uin = 5.6
- Press F6 to recalculate
or
- Decrease the input voltage to 125V : Uin = 1
- Press F6 to recalculate
- Decrease the form factor to 0.711 (q = 0.7) Press F6 to recalculate
- Press F6 to recalculate
- Secondary current ripple is: Bn/(B0-Bn) = 100*0.091/(.197-0.091) = 86%<100%
The following table shows the summery of the most important parameters, calculated by
program in the test mode. Note that the relative switch-on period (q) was changed in order
to get the nominal input voltage as by a voltage controller.
Ui
V |
Iprms
A |
2xIsrms
A |
2xUodc
V |
2xIodc
A |
Pcu
W |
Pfe
W |
q |
Ripple
% |
dTcu
°K |
125 |
1.25 |
9.22 |
12.0 |
5.0 |
4.4 |
0.29 |
0.7 |
16 |
58 |
125 |
0.66 |
4.82 |
12.3 |
2.58 |
1.04 |
0.31 |
0.7 |
30 |
20 |
296 |
0.66 |
7.47 |
12.2 |
5.12 |
1.52 |
0.96 |
0.5 |
44 |
34 |
296 |
0.366 |
4.08 |
12.2 |
2.58 |
0.44 |
1.03 |
0.5 |
85 |
21 |
700 |
0.4 |
6.9 |
12.3 |
5.2 |
0.95 |
1.83 |
0.3 |
86 |
35 |
700 |
0.23 |
3.99 |
12.0 |
2.53 |
0.29 |
1.14 |
0.2 |
>100 |
20 |
In order to get the constant total losses in the whole range of the input voltage,
select the ferrite and the operation frequency at the nominal input voltage so, that you
get approximately Pfe = Pcu
- f the design data is not satisfactory, then there are two ways by which we can implement
the desired correction:
- You can return to the input mask (function key F2), correct the input data and redesign
the transformer.
- Or you can access the test program (function key F5), modify the designed transformer
manually and redesign the transformer by that means.
- On completion of the design work, you can print out the design data on-line, or save it
on your local PC and print it out off-line. The output data file from this design example,
CAL0010E.TK2, is supplied together with this document. Copy it
into the directory in which your Rale demo program is installed.
Tips & Tricks
Rounding off the number of windings
With a flyback transformer, the procedure for rounding off the number of windings
differs from that employed with a "normal" transformer.
- You start by modifying the induction or ripple of the secondary current until the
desired number of secondary windings is achieved.
- Next, we correct the nominal primary voltage until the desired number of primary
windings is reached.
- In the test program, finally, the number of windings is rounded off manually.
Copper strip instead of litz
A copper strip can replace a litz. The strip thickness should correspond to the wire
diameter of the litz. Strip width should be matched to the width of the bobbin. The number
of strips connected in parallel is determined in accordance with the following
illustration.

Calibrating the inductance of the primary winding
The inductance of the first tapping of the primary winding must be calibrated at the
operating frequency of the flyback transformer. The calculated gap is a guideline value
only, and has to be modified during calibration so that the designed (prescribed)
inductance ( 2.63 mH) is correct.

How do I design a flyback transformer, without voltage controller, for input voltage
range +-20% and load variation +10% to 100%?
- Input voltage = (Upmin*Upmax)^0.5 at
- Form factor = 1 (q= 0.5)
- dI/Io = 10% (Ripple of the current)
Note that the output voltage alters proportional to the input voltage and does not
depend of the load
How do I design a flyback transformer for "constant output power", without
voltage controller, for input voltage range +-20% and load variation +10% to 100%?
- Input voltage = Upmax
- Maximal otput voltage
- Maximal output current
- Form factor = 1 (q= 0.5)
- dI/Io = 100% (Ripple of the current)
Note that the output voltage alters proportional to the input voltage. If you increase
in test mode the resitaance of the load, the output voltage alters so, that the output
power stays "constant".
.How do I design a flyback transformer , with voltage controller, for input voltage
range +-10% and for constant resistance of the load?
- Input voltage = Umin
- Nominal otput voltage
- Nominal output current
- Form factor = 1 (q= 0.5)
- dI/Io = 100% (Ripple of the current)
How do I design a smoothing choke for current ripple of 20%, output voltage 12Vdc
and output current 5Adc?
- Input voltage = Uout + Udiode = 12 + 0.8 = 12.8
- Form factor = 1 (q=0.5)
- Secondary circuit = 35
- Nominal output voltage = 12V
- Nominal output current = 5A
- dI/Io = 20% (Ripple of the current)
- Udiode = 0.8V
- Induction = 0.20 - 0.25T
- Not high quality ferrite
After the design you have to:
- increase the number of the in parallel (by program calculated) wires of the primary
winding for the factor 1.41
- leave out the secondary winding
Note that this choke can be used in the rectifier circuit of a forward transformer.
<Back>
|